30 U.S.C. § 866 — Trailing cables
submitted 57 years ago by Pub. L. 91-173 to r/title-30-MINERAL-LANDS-AND-MINING · 376 words · no verdicts yet
This section sets safety rules for trailing cables in coal mines, including their construction, protection, splices, and connections.
Trailing cables used in coal mines shall meet the requirements established by the Secretary for flame-resistant cables.
Short-circuit protection for trailing cables shall be provided by an automatic circuit breaker or other no less effective device approved by the Secretary of adequate current-interrupting capacity in each ungrounded conductor. Disconnecting devices used to disconnect power from trailing cables shall be plainly marked and identified and such devices shall be equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected.
When two or more trailing cables junction to the same distribution center, means shall be provided to assure against connecting a trailing cable to the wrong size circuit breaker.
One temporary splice may be made in any trailing cable. Such trailing cable may only be used for the next twenty-four hour period. No temporary splice shall be made in a trailing cable within twenty-five feet of the machine, except cable reel equipment. Temporary splices in trailing cables shall be made in a workmanlike manner and shall be mechanically strong and well insulated. Trailing cables or hand cables which have exposed wires or which have splices that heat or spark under load shall not be used. As used in this subsection, the term “splice” means the mechanical joining of one or more conductors that have been severed.
When permanent splices in trailing cables are made, they shall be—
mechanically strong with adequate electrical conductivity and flexibility;
effectively insulated and sealed so as to exclude moisture; and
vulcanized or otherwise treated with suitable materials to provide flame-resistant qualities and good bonding to the outer jacket.
Trailing cables shall be clamped to machines in a manner to protect the cables from damage and to prevent strain on the electrical connections. Trailing cables shall be adequately protected to prevent damage by mobile equipment.
Trailing cable and power cable connections to junction boxes shall not be made or broken under load.
Source credit: (Pub. L. 91–173, title III, § 306, Dec. 30, 1969, 83 Stat. 779.)
- 1969Enacted · Pub. L. 91-173 · 83 Stat. 779
A history note hasn’t been published yet. The record shows enactment by Pub. L. 91-173 on 1969-12-30.
all 0 arguments · sorted by: best
no arguments yet — make the first case