30 U.S.C. § 869Underground low- and medium-voltage alternating current circuits

submitted 57 years ago by Pub. L. 91-173 to r/title-30-MINERAL-LANDS-AND-MINING · 618 words · no verdicts yet

in plain englishAI-generated · not legal advice

This section sets grounding, circuit-breaker, ground-check, cable, and connection rules for underground low- and medium-voltage alternating-current circuits.

(a) Circuits serving three-phase alternating-current equipment must have properly tested and maintained circuit breakers with enough interrupting capacity and protection against under-voltage, grounded phase, short circuit, and overcurrent. (b) Underground three-phase circuits must have a direct or derived neutral grounded through a suitable resistor at the power center. A grounding circuit from the grounded side of that resistor must run with the power conductors and ground the frames of all equipment supplied by the circuit. The Secretary or representative may allow an ungrounded circuit for stationary equipment if it is steel-armored or in grounded rigid steel conduit throughout. The resistor must limit ground-fault current to 25 amperes, be continuously rated for maximum fault current, and be insulated from ground for the system’s phase-to-phase voltage. (c) Six months after the operative date, resistance-grounded systems must have a fail-safe ground-check circuit that continuously monitors grounding continuity and opens the breaker if the ground or pilot-check wire breaks. An equally effective approved device may be used. The Secretary may allow up to a 12-month extension for a particular mine if the equipment is unavailable. Couplers must break the ground-check conductor first and the ground conductors last when uncoupled. (d) Disconnecting devices must be installed with the breaker to show visibly that power is disconnected. Mobile-equipment trailing cables must have ground conductors totaling at least one-half the power conductor’s cross-sectional area and, after six months, an insulated ground-check conductor or equally effective approved device. The Secretary may allow a mine-specific extension of up to 12 months if equipment is unavailable. Cable splices must preserve continuity of every component. (e) Single-phase loads must be connected phase to phase. (f) Circuit breakers must be marked for identification. (g) Medium-voltage trailing cables must have grounding conductors, a ground-check conductor, and grounded metallic shields around each power conductor or over the assembly. Cable-reel equipment may use unshielded cables if their insulation is rated at least 2,000 volts.
the actual law source: uscode.house.gov ↗public domain
(a) Circuits providing power for three-phase equipment; circuit breakers

Low- and medium-voltage power circuits serving three-phase alternating current equipment shall be protected by suitable circuit breakers of adequate interrupting capacity which are properly tested and maintained as prescribed by the Secretary. Such breakers shall be equipped with devices to provide protection against under-voltage, grounded phase, short circuit, and over-current.

(b) Circuits used underground; direct neutral grounds; ground conductors for frames; exceptions; grounding resistors

Low- and medium-voltage three-phase alternating-current circuits used underground shall contain either a direct or derived neutral which shall be grounded through a suitable resistor at the power center, and a grounding circuit, originating at the grounded side of the grounding resistor, shall extend along with the power conductors and serve as a grounding conductor for the frames of all the electrical equipment supplied power from that circuit, except that the Secretary or his authorized representative may permit ungrounded low- and medium-voltage circuits to be used underground to feed such stationary electrical equipment if such circuits are either steel armored or installed in grounded rigid steel conduit throughout their entire length. The grounding resistor, where required, shall be of the proper ohmic value to limit the ground fault current to 25 amperes. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.

(c) Inclusion of fail safe ground check circuits in resistance ground systems; operative functions; time extension; couplers for power circuits; guidelines for construction

Six months after the operative date of this subchapter, low- and medium-voltage resistance grounded systems shall include a fail safe ground check circuit to monitor continuously the grounding circuit to assure continuity which ground check circuit shall cause the circuit breaker to open when either the ground or pilot check wire is broken, or other no less effective device approved by the Secretary or his authorized representative to assure such continuity, except that an extension of time, not in excess of twelve months, may be permitted by the Secretary on a mine-by-mine basis if he determines that such equipment is not available. Cable couplers shall be constructed so that the ground check continuity conductor shall be broken first and the ground conductors shall be broken last when the coupler is being uncoupled.

(d) Disconnecting devices installed in conjunction with circuit breakers; purpose; trailing cables for mobile equipment; guidelines for construction; time extension; splices

Disconnecting devices shall be installed in conjunction with the circuit breaker to provide visual evidence that the power is disconnected. Trailing cables for mobile equipment shall contain one or more ground conductors having a cross sectional area of not less than one-half the power conductor, and, six months after the operative date of this subchapter, an insulated conductor for the ground continuity check circuit or other no less effective device approved by the Secretary or his authorized representative to assure such continuity, except that an extension of time, not in excess of twelve months may be permitted by the Secretary on a mine-by-mine basis if he determines that such equipment is not available. Splices made in the cables shall provide continuity of all components.

(e) Connections of single phase loads

Single phase loads shall be connected phase to phase.

(f) Circuit breakers; markings

Circuit breakers shall be marked for identification.

(g) Trailing cables for medium voltage circuits; guidelines for construction

Trailing cables for medium voltage circuits shall include grounding conductors, a ground check conductor, and ground metallic shields around each power conductor or a grounded metallic shield over the assembly, except that on equipment employing cable reels, cables without shields may be used if the insulation is rated 2,000 volts or more.

Source credit: (Pub. L. 91–173, title III, § 309, Dec. 30, 1969, 83 Stat. 782.)