ALLcrimesfood&drugstaxestelecomcommercehealthconservationtransportationagricultureveteransbrowse all titles »
0

30 U.S.C. § 868Underground high-voltage distribution

submitted 57 years ago by Pub. L. 91-173 to r/title-30-MINERAL-LANDS-AND-MINING · 1,165 words · no verdicts yet

in plain englishAI-generated · not legal advice

This section sets safety rules for underground high-voltage circuits, cables, equipment, grounding, and movement.

(a) High-voltage circuits entering a coal mine underground must have properly tested and maintained breakers with enough interrupting capacity and protection against under-voltage, grounded phase, short circuit, and overcurrent. (b) Circuits supplying underground high-voltage equipment must have a direct or derived neutral grounded through a resistor at the source transformer. A grounding circuit from the resistor’s grounded side must run with the power conductors and ground equipment frames. The Secretary or representative may allow an ungrounded circuit for stationary equipment if it is steel-armored or in grounded rigid steel conduit throughout and the exception is not hazardous. Disconnecting devices must be within 100 feet on the surface of each entry point and must visibly show disconnection, unless the Secretary allows a greater, more accessible distance without hazard. (c) A required resistor must limit voltage drop outside it in the grounding circuit to 100 volts or less during a fault, be continuously rated for maximum fault current, and be insulated from ground for the system’s phase-to-phase voltage. (d) Six months after the operative date, resistance-grounded systems must have a fail-safe ground-check circuit that continuously monitors continuity and opens the breaker if the ground or pilot wire breaks. An equally effective approved device may be used. The Secretary may allow a mine-specific extension of up to 12 months if equipment is unavailable. (e) Underground high-voltage cables in resistance-grounded systems must have a metallic shield around each power conductor, ground conductors totaling at least one-half the power conductor’s cross-sectional area, and an insulated internal or external No. 8 AWG-or-larger ground-check conductor. Cables must fit the intended current and voltage, and splices must preserve every component’s continuity. (f) Medium- and high-voltage couplers must be three-phase with a full metal shell, unless the Secretary allows equally effective nonmetal couplers under guidelines. They must fit the expected voltage and current. Exposed metal must be grounded to the cable’s ground conductor. The design must break the ground-check conductor first and ground conductors last during uncoupling. (g) Single-phase loads, including transformer primaries, must connect phase to phase. (h) Underground high-voltage transmission cables may be installed only in regularly inspected air courses and haulageways. They must be covered, buried, or placed to prevent damage; guarded where people regularly work or pass below unless at least 6½ feet above the floor or rail; anchored securely; insulated properly; guarded at ends; and covered, insulated, or placed to prevent contact with trolley wires and other low-voltage circuits. (i) Disconnecting devices must be at the start of high-voltage branch lines and visibly show that the circuit is deenergized when open. (j) Underground breakers and disconnecting switches must be marked for identification. (k) High-voltage trailing cables may not have temporary splices; permanent splices must meet § 866(e). Terminations and splices in other high-voltage cables must follow the manufacturer’s specifications. (l) Frames, supports, and enclosures of underground high-voltage equipment, and high-voltage equipment supplying it from resistance-grounded systems, must be effectively grounded to the high-voltage ground. (m) Power centers and portable transformers must be deenergized before moving. The Secretary may allow energized movement when other power sources are unavailable and another equal or greater hazard would otherwise result, if a qualified person supervises, examines the equipment beforehand, confirms approved grounding and other protection, and a record is kept. Nontrailing high-voltage cables may not be moved while energized. If the permitted energized movement occurs, attached energized cables may be moved only by a qualified person wearing approved, tested wireman’s gloves.
the actual law source: uscode.house.gov ↗public domain
(a) Circuits entering underground areas of mines; circuit breakers

High-voltage circuits entering the underground area of any coal mine shall be protected by suitable circuit breakers of adequate interrupting capacity which are properly tested and maintained as prescribed by the Secretary. Such breakers shall be equipped with devices to provide protection against under-voltage, grounded phase, short circuit, and overcurrent.

(b) Circuits extending underground and supplying equipment; direct neutral grounds; ground conductors for frames, exceptions; location of disconnection devices, exceptions

High-voltage circuits extending underground and supplying portable, mobile, or stationary high-voltage equipment shall contain either a direct or derived neutral which shall be grounded through a suitable resistor at the source transformers, and a grounding circuit, originating at the grounded side of the grounding resistor, shall extend along with the power conductors and serve as a grounding conductor for the frames of all high-voltage equipment supplied power from that circuit, except that the Secretary or his authorized representative may permit ungrounded high-voltage circuits to be extended underground to feed stationary electrical equipment if such circuits are either steel armored or installed in grounded, rigid steel conduit throughout their entire length, and upon his finding that such exception does not pose a hazard to the miners. Within one hundred feet of the point on the surface where high-voltage circuits enter the underground portion of the mine, disconnecting devices shall be installed and so equipped or designed in such a manner that it can be determined by visual observation that the power is disconnected, except that the Secretary or his authorized representative may permit such devices to be installed at a greater distance from such area of the mine if he determines, based on existing physical conditions, that such installation will be more accessible at a greater distance and will not pose any hazard to the miners.

(c) Grounding resistors

The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.

(d) Inclusion of fail safe ground check circuits in resistance grounded systems; operative functions; time extension

Six months after the operative date of this subchapter, high-voltage, resistance grounded systems shall include a fail safe ground check circuit to monitor continuously the grounding circuit to assure continuity and the fail safe ground check circuit shall cause the circuit breaker to open when either the ground or pilot check wire is broken, or other no less effective device approved by the Secretary or his authorized representative to assure such continuity, except that an extension of time, not in excess of twelve months, may be permitted by the Secretary on a mine-by-mine basis if he determines that such equipment is not available.

(e) Underground cables used in resistance grounded systems; metallic shields for power conductors; standards; splices
(1)

Underground high-voltage cables used in resistance grounded systems shall be equipped with metallic shields around each power conductor, with one or more ground conductors having a total cross-sectional area of not less than one-half the power conductor, and with an insulated internal or external conductor not smaller than No. 8 (AWG) for the ground continuity check circuit.

(2)

All such cables shall be adequate for the intended current and voltage. Splices made in such cables shall provide continuity of all components.

(f) Couplers for power circuits; guidelines for construction

Couplers that are used with medium-voltage or high-voltage power circuits shall be of the three-phase type with a full metallic shell, except that the Secretary may permit, under such guidelines as he may prescribe, no less effective couplers constructed of materials other than metal. Couplers shall be adequate for the voltage and current expected. All exposed metal on the metallic couplers shall be grounded to the ground conductor in the cable. The coupler shall be constructed so that the ground check continuity conductor shall be broken first and the ground conductors shall be broken last when the coupler is being uncoupled.

(g) Connections of single-phase loads

Single-phase loads, such as transformer primaries, shall be connected phase to phase.

(h) Installation of underground transmission cables

All underground high-voltage transmission cables shall be installed only in regularly inspected air courses and haulageways, and shall be covered, buried, or placed so as to afford protection against damage, guarded where men regularly work or pass under them unless they are six and one-half feet or more above the floor or rail, securely anchored, properly insulated, and guarded at ends, and covered, insulated, or placed to prevent contact with trolley wires and other low-voltage circuits.

(i) Disconnection devices; location; visual observation of position of switch

Disconnecting devices shall be installed at the beginning of branch lines in high-voltage circuits and equipped or designed in such a manner that it can be determined by visual observation that the circuit is deenergized when the switches are open.

(j) Circuit breakers and disconnection devices; markings

Circuit breakers and disconnecting switches underground shall be marked for identification.

(k) Splices in cables used as trailing cables; terminations and splices in other cables

In the case of high-voltage cables used as trailing cables, temporary splices shall not be used and all permanent splices shall be made in accordance with section 866(e) of this title. Terminations and splices in all other high-voltage cables shall be made in accordance with the manufacturer’s specifications.

(l) Grounding of frames of underground equipment

Frames, supporting structures, and enclosures of stationary, portable, or mobile underground high-voltage equipment and all high-voltage equipment supplying power to such equipment receiving power from resistance grounded systems shall be effectively grounded to the high-voltage ground.

(m) Moving of power centers, transformers, and cables; deenergizing; exceptions; safety guidelines; record of examinations

Power centers and portable transformers shall be deenergized before they are moved from one location to another, except that, when equipment powered by sources other than such centers or transformers is not available, the Secretary may permit such centers and transformers to be moved while energized, if he determines that another equivalent or greater hazard may otherwise be created, and if they are moved under the supervision of a qualified person, and if such centers and transformers are examined prior to such movement by such person and found to be grounded by methods approved by an authorized representative of the Secretary and otherwise protected from hazards to the miner. A record shall be kept of such examinations. High-voltage cables, other than trailing cables, shall not be moved or handled at any time while energized, except that, when such centers and transformers are moved while energized as permitted under this subsection, energized high-voltage cables attached to such centers and transformers may be moved only by a qualified person and the operator of such mine shall require that such person wear approved and tested insulated wireman’s gloves.

Source credit: (Pub. L. 91–173, title III, § 308, Dec. 30, 1969, 83 Stat. 780.)

history & why it existsrecord from the source credit
  • 1969Enacted · Pub. L. 91-173 · 83 Stat. 780

A history note hasn’t been published yet. The record shows enactment by Pub. L. 91-173 on 1969-12-30.

all 0 arguments · sorted by: best

0/280

no arguments yet — make the first case